Without DG | With type I DG (kW) | With type II DG (kVAR) | With type III DG (kVA) at 0.9 pf lag | With type III DG (kVA) at upf pf | |
---|---|---|---|---|---|
Location | – | 6 | 6 | 6 | 6 |
DG size | – | 675.248 | 682.344 | 907.785 | 675.248 |
TLP (kW) | 61.7933 | 45.8035 | 45.3228 | 33.385 | 45.8035 |
TLQ (kVAR) | 57.2969 | 41.8809 | 41.4261 | 29.8915 | 41.8809 |
Vmin | 0.9445 | 0.9527 | 0.9526 | 0.9590 | 0.9527 |