From: Optimal DG placement for benefit maximization in distribution networks by using Dragonfly algorithm
 | With DG | |
---|---|---|
Voltage sensitivity index method (Murthy and Kumar 2013) | Proposed method | |
DG location | 65 | 61 |
DG size (kVA) | 1750 | 2217.3 |
TLP (kW) | 65.4502 | 27.9636 |
TLR (kVAR) | 35.625 | 16.4979 |
Vmin (p.u.) | 0.969302 | 0.9728 |
Cost of Energy losses ($) | 5268.4297 | 2249.2 |
Cost of PDG ($/MW h) | 31.75 | 40.1 |
Cost of QDG ($/MVAR h) | 3.083 | 4.48 |