Related works
In this section, the existing techniques and frameworks related to renewable energy penetration and damping ratio reduction are presented.
Edrah et al. (2015) investigated the impact of DFIG based on its rotor angle stability for the integration of wind power with the power systems. In this design, the rotor-side converter (RSC) and grid-side converter (GSC) were utilized to provide the reactive power support to the grid during the fault occurrence. Here, a Western System Coordinating Council (WSCC) was utilized to validate the suggested approach under small and large disturbances. Mehta et al. (2015) designed a controller using particle swarm optimization (PSO) algorithm for developing the DFIG-based wind power system. The intention of this paper was to reduce the oscillations in both electromagnetic torque and rotor currents. Here, the oscillation modes of DFIG were analyzed under varying operating conditions such as grid strength and wind speed. In this design, the reason of using MPPT was to extract the maximum power from the wind. Moreover, the torque control scheme was utilized to modify the electromagnetic torque of the generator based on the speed of wind. Also, the voltage control scheme satisfied the requirements of reactive power compensation and too high or too low terminal voltage. Sreedharan et al. (2015) utilized a PSO algorithm for adjusting the grid control settings by maximizing the renewable penetration of all layers in grid. The main focus of this paper was to maintain both line and voltage stability by stabilizing the grid. Here, the optimal loading pattern was identified to determine the instantaneous penetration based on the fitness function. Also, the bus used for connecting the wind farm index was identified by calculating the placement index. Chatterjee et al. (2016) designed a teaching learning-based optimization (TLBO) technique for analyzing the signal stability of DFIG wind power system. Here, the dynamic performance of the DFIG system was controlled by the use of proportional–integral (PI) controllers. The main contribution of this paper was to reduce the damping phenomena oscillation by analyzing the rotor currents and fluctuations in the electromagnetic torque.
Tang et al. (2015) implemented a new controller design by using a goal representation heuristic dynamic programming (GrHDP) for increasing the system transient stability under different fault conditions. Here, the interaction between the controller and power plant was analyzed by using an adaptive dynamic programming (ADP) technique. The control mechanisms that are used in this work were power optimization and limitation mechanism, which were responsible for controlling the active and reactive power of the DFIG. The suggested GrHDP based contains three modules such as action network, critic network and reference network. However, this paper required to improve the stability of the large-scale interconnected power system. Byrne et al. (2016) quantified the impact of wind and photovoltaic generation on the inter-area modes of American power system. Here, an optimal control scheme was utilized to mitigate the modes and the communication delay of the control system. The main focus of this paper was to improve the stability for the lower frequency NS-A mode. Krishan et al. (2014) investigated the penetration of distributed solar PV- and DFIG-based wind generation in power systems. Here, different modes such as local mode, inter-area mode and critical mode of the system were allocated by using the grid-connected distributed PV generation. In this design, the solar photovoltaic generator (SPVG) system was connected with grid, which contains the solar panels, DC/DC and DC/AC converters.
Erdinc et al. (2015) provided an overview about the insulator power system structures and operational requirements under an increased penetration of renewable energy source. In this paper, an overview about the insular power system structure was provided. Here, the frequency and voltage stability measures were improved by reducing the inertia in an isolated power system. Sahu et al. (2014) developed a power system stabilizer (PSS) by using PSO technique for increasing the damping and steady-state stability margin. The main focus of this paper was to maintain the system stability by optimally tuning the parameters of PSO. The measures such as settling time, speed and overshoot of the machines were reduced under varying disturbances. Pandey et al. (2014) introduced a robust controller for regulating the frequency of the hybrid power system by using the PSO algorithm. In this design, two types of configurations were considered such as hybrid configuration and two-area interconnected power system, in which the thermal power system (TPS) was integrated with DG during the hybrid configuration. Moreover, the linear matrix inequalities (LMI) and its parameters were considered in the suggested control scheme. The robustness of the controller was validated under varying load disturbances, wind power and parameter variations.
Ray et al. (2016) designed a robust power system stabilizer (PSS) by using a swarm and bacterial foraging-based optimization techniques for maintaining the stability of the power system. In this design, a single machine infinite bus (SMIB) was considered to analyze the stability of the system. The major intention of using the optimization techniques was to optimize the parameters that are used for the controller design. Here, the settling time and peak overshoot measures were considered to analyze the frequency oscillations of the system. Rahman et al. (2015) analyzed the operation and controlling strategies of integrated distributed energy sources for reducing the emissions and resistive losses. Here, five distributed energy resources and its controlling strategies were investigated for modernized power systems. Liu et al. (2014) studied the impact of large-scale wind power integration on small signal stability. Based on wind farm integration coupled with a single-machine infinite-bus system, it was observed that, compared with the synchronous generator, a wind farm greatly reduces the small signal stability region boundary and the small signal stability of the power system. Yan and Sekar (2002) studied the effectiveness of the linear models of power systems and observed that linear models are delivering results that are close to the full nonlinear models. Here the linear model results were compared with the correct results after complete convergence is obtained for the IEEE 14-bus system.
From the survey, it is observed that the traditional techniques have both benefits and demerits. But, it mainly lacks with the limitations of reduced efficiency, increased complexity and cost. To solve these issues, this paper aims to develop a multi-level optimization by adjusting the grid parameters assuring grid stability.
Proposed method
In this section, the clear description about the proposed scheme is presented with its flow representation. The main objectives of this work are to improve the renewable energy penetration meeting all the grid requirements and to improve the small signal stability of the grid at maximum renewable penetration by a quite unique approach and methodology.
This methodology comprises two stages, in which the particle swarm optimization (PSO) algorithm is implemented in the first stage for maximizing the penetration of the renewable resources such as wind and solar by keeping all parameters based on the grid requirements. Then, the small signal stability of the system is optimized in the second stage with maximum renewable energy penetration in which the best location is identified by using WFPI for connecting the wind farm (Sreedharan et al. 2010), and the solar generation is fixed by considering the limiting values of voltage and bus load absorption capability. These two stages are applied on an IEEE 14-bus system and Kerala grid with solar and wind power. The flow of the proposed system is depicted in Fig. 1.
In this design, the multi-objective problem is considered for maximizing the renewable energy penetration and optimizing the damping ratios by fulfilling the stability constraints based on the following equation:
$${\text{Maximize}}\quad J \left( {x, u} \right) = \left\{ {J_{1} \left( {x, u} \right) + J_{2} \left( {x, u} \right)} \right\}$$
(1)
where J1 and J2 indicate two objective functions, which represents the renewable energy penetration and damping ratio optimization, x represents the vector of dependent variables and u is the vector of control variables.
Renewable energy penetration
The main aim of optimization is to increase the share of renewable energy in the grid, which is illustrated as follows:
$${\text{Maximize}}\quad J_{1 } \left( {x, u} \right) = \left\{ {\exp \;\gamma \left| {\lambda_{\text{f}} - \lambda_{\text{f}}^{\max } } \right| \lambda_{\text{f}} \in 1,\lambda_{\text{f}}^{\max } } \right\}$$
(2)
Subjected to
$${\text{VL}} = {\mathop \sum \limits_{i = 1}^{\text{Nl}}} {\text{OLL}}_{i} *{\mathop \sum \limits_{j = 1}^{\text{Nb}}} {\text{BVV}}_{j}$$
(3)
$${\text{OLL}}_{i} = \left\{ {\begin{array}{*{20}ll} 1 &\quad {{\text{if}}\quad P_{ij} \le P_{ij}^{\max } } \\ {\left\{ {\exp \left[ {\tau_{\text{OLL}} \left| {1 - \frac{{P_{ij} }}{{P_{ij}^{\max } }}} \right|} \right]} \right\}} &\quad {\text{Otherwise}} \\ \end{array} } \right\}$$
(4)
$${\text{BVV}}_{j} = \left\{ {\begin{array}{*{20}ll} 1 &\quad {{\text{if}}\quad 0.95 \le V_{b} \le 1.05} \\ {\left\{ {{ \exp }\left[ {\tau_{\text{BVV}} \left| {1 - V_{b} } \right|} \right]} \right\}} &\quad {\text{Otherwise}} \\ \end{array} } \right\}$$
(5)
where λf = load factor = 1 as base case, γ = coefficient to adjust the slope of the function \(\lambda_{\text{f}}^{\max }\) = max. limit of load factor. VL defines the thermal and bus violation limit factor, OLLi is the overload line factor of line i, BVVj indicates the bus voltage violation factor at bus j, Nl and Nb are the total number of transmission lines and total number of buses in the system, respectively, and \(\tau_{\text{BVV}}\) and \(\tau_{\text{OLL}}\) are the coefficients that used to adjust the slope of functions. The load factor \(\lambda_{\text{f}}\) reflects the variation of power loads PDi and QDj, which are defined as follows:
$$P_{Di} \left( {\lambda_{f} } \right) = \lambda_{f} P_{Di } : Q_{Di} \left( {\lambda_{f} } \right) = \lambda_{\text{f}} Q_{D}$$
(6)
Damping ratio optimization
The damping ratio \(\zeta = \frac{ - \sigma }{{\sqrt {\sigma^{2} + \omega^{2} } }}\) represents the decay of amplitude of oscillations, and a negative real part of a complex pair eigenvalues, i.e., \(\lambda = \sigma \pm j\omega\) indicates that the oscillations are damped. To optimize the damping ratio, J2 is maximized as follows:
$${\text{Max}}\quad J_{2} \left( {x, u} \right) = \mathop \sum \limits_{i = 1}^{n} \zeta_{i}$$
(7)
The dependent variables in the optimization are the exciter amplifier gain Ka, exciter stabilizer gain Kf and turbine governor droop R.
The power flow problem is formulated by obtaining the solution of a nonlinear set of equations, which is shown in below:
$$\dot{x} = 0 = f \left( {x,y} \right)\quad {\text{and}}\quad 0 = g\left( {x,y} \right)$$
(8)
where y is defined as the vector of algebraic variables (i.e., voltage amplitude (V) and phases (\(\theta\))).
-
1.
Equality constraints
Here, the equality constraints are used in the optimization problem, in which the total real and reactive power generations PGi and QGi are estimated. Then, each generator maintains the load generation profile as shown in below:
$$P_{Gi} = P_{Li} + V_{i} \mathop \sum \limits_{j = 1}^{N} V_{j} \left( {G_{ij} \cos \delta_{ij} + B_{ij} \sin \delta_{ij} } \right)$$
(9)
$$Q = Q_{Li} + V_{i} \mathop \sum \limits_{j = 1}^{N} V_{j} \left( {G_{ij} \sin \delta_{ij} + B_{ij} \cos \delta_{ij} } \right)$$
(10)
where i = 1, 2 … N;
-
2.
Inequality constraints
In this system, the parameters such as apparent power flow limit, bus voltage limit, slack generator power output limit and wind power output limit are considered as the inequality constraints.
-
Apparent power flow limit—\(S_{ij} \le S_{ij\max }\)
-
Bus voltage limit—\(V_{i\min } \le V_{i} \le V_{i\max }\)
-
Slack generator power output limit—\(\begin{aligned} P_{\text{slack}} & \le P_{\text{slackmax}} \\ Q_{\text{slack}} & \le Q_{\text{slackmax}} \\ \end{aligned}\)
-
Wind power output limit—\(\begin{aligned} P_{\text{wind}} & \le P_{\text{windmax}} \\ Q_{\text{wind}} & \le Q_{\text{windmax}}. \\ \end{aligned}\)
The dependent variables used in this analysis are the power of generator buses, voltage of load buses, reactive power output of generators and apparent power flow. The control variables that considered in this design are the voltages of PV bus, generation bus voltage, angle, loads, voltage of SPV, voltage gain and pitch gain of DFIG.
-
3.
Fast voltage stability indices (FVSI)
The FVSI assures that no bus can get collapsed due to the problem of overloading. Taking the symbols ‘i’ as the sending bus and ‘j’ as the receiving bus, the fast voltage stability index FVSI can be defined as follows:
$${\text{FVSI}} = \frac{{4Z^{2} Q_{j} }}{{V_{i}^{2} X}}$$
(11)
where Z indicates the line impedance, X is the line reactance, Qj is the reactive power at the receiving end bus and Vi denotes the sending end bus voltage.
-
4.
Line stability index
The line stability index Lmn is calculated based on a power transmission concept in a single line. Taking the symbols ‘s’ as the sending and ‘r’ as the receiving end of the line, Lmn is defined as follows:
$$L_{mn} = \frac{{4Q_{\text{r}} X}}{{\left[ {\left| {V_{\text{s}} } \right|\sin \left( {\theta - \delta } \right)^{2} } \right]}}$$
(12)
where X is the line reactance, Qr defines the reactive power at the receiving end of transmission line, Vs denotes the sending end voltage, \(\theta\) is the line impedance angle, and \(\delta\) is the angle difference between the supply voltage and receiving voltage. The value of Lmn must be less than the value of 1 for maintaining the system stability.
-
5.
Line stability factor
The line stability factor (LQP), based on a power transmission concept in a single line, assures the system stability, which is expressed as follows:
$${\text{LQP}} = 4\left( {\frac{X}{{V_{i}^{2} }}} \right)\left( {\frac{X}{{V_{i}^{2} }} P_{i}^{2} + Q_{j} } \right)$$
(13)
where X is the line reactance, Vi is the voltage at the sending end bus, Pi is the active power at the sending end bus and Qj is the reactive power at the receiving end bus. To maintain a secure condition, LQP should be maintained below 1.
-
6.
Wind farm placement index
The bus at which the wind farm to be placed was identified by the calculation of wind farm placement index (WFPI) by taking into account the parameters such as voltage limits and voltage stability, wind speed, interconnecting cable length and bus load absorption capability (Sreedharan et al. 2010). Interconnection bus should not be weak (higher the voltage stronger the bus), and tangent vector of node voltage determines the relative weakness of the bus. A bus bar within the major power system grid is stronger than bus in a separate small mesh of load busses connecting to a single node of the major grid. The wind farm placement index is given by
$$I_{wpj} = R_{wj} + C_{\text{v}} R_{{{\text{v}}j}} + (1/C_{\text{VSI}} )R_{{{\text{VSI}}j}} + \left( {\frac{1}{{C_{\text{l}} }}} \right)R_{ij} + I_{{{\text{grid}}j}}$$
(14)
where Rwj is the wind speed rank of bus j, Cv is the voltage constant, Rvj is the voltage rank of bus j, CVSI is the voltage sensitivity index constant, RVSIj is the voltage sensitivity index rank of bus j, Cl is the interconnection cable length constant, Rij is the interconnection cable length rank of bus j and Igridj is the index of grid connection of bus j.
-
Rwj = 1; if 6 ≤ wj ≤ 9; Rwj = 2 if wj ≤ 6; Rwj = 3 if wj ≥ 9.
-
Rvj = 0; if j = generator bus or having SVC.
-
Else rank bus bars from higher voltage level to lower.
-
To obtain RVSIj, find 1/abs (VSI); rank bus bars from higher value to lower.
-
(The highest sensitivity index results in the weakest bus and vice versa).
-
To obtain Rij, find 1/(cable length); rank bus bars from higher value to lower.
-
Igridj = 0; for major power system grid else Igridj == number of buses in the small mesh of load buses getting connected to the single node of the major grid.
-
Cv = 1.5
-
CVSI = 0.375 × number of buses considered suitable for wind farm placement.
In stage 2, the damping ratio with maximum renewable penetration is maximized by keeping all parameters in a safe limit. The control variables that are used in the optimization of damping ratios are the exciter amplifier gain Ka, exciter stabilizer gain Kf and turbine governor droop R. Here, the Newton–Raphson model is mainly used to calculate the eigenvalues and damping ratio.
Particle swarm optimization
PSO is one of the widely used optimization techniques that works, based on swam intelligence, in which the search is performed based on the speed of particle. The major reasons of using PSO are: it does not require any overlapping and mutation calculation, simple calculation and very fast searching speed. The PSO is a kind of population-based searching procedure that uses the particles to change their position in the problem space, which is shown in below:
$$V_{i}^{k + 1} \omega^{k} V_{i}^{k} + a_{1} r_{1} \times \left( {P_{bi}^{k} - X_{i}^{k} } \right) + a_{2} r_{2} \times \left( {G_{bi}^{k} - X_{i}^{k} } \right)$$
(15)
where \(P_{bi}\) represents the local best particle, \(G_{bi}\) indicates the global best particle, \(\omega\) indicates the inertia weight function, a1 and a2 are the acceleration constants and r1 and r2 are the random values that lies between 0 and 1. The particle’s position is updated as follows:
$$X_{i}^{k + 1} = X_{i}^{k} + V_{i}^{k + 1}$$
(16)
The search space in PSO is multi-dimensional in nature, in which each particle and its position are updated based on the experience of neighboring particles. The procedure of PSO is illustrated as follows:
Case study
The proposed system is tested based on the following case studies:
Renewable resources integrated with IEEE 14-bus system
This system contains three synchronous generators connected at the buses 1, 2 and 8, where the automatic voltage regulator (AVR) and turbine governors of type II are connected with the sixth-order model generators at buses 1 and 2. The wind farm placement index calculation assumed that wind farm was located at an equidistant point from all the buses and identified bus 3 as the most suitable bus, and accordingly, the variable speed wind turbine generating system with DFIG is placed at bus 3 through a transformer and bus 15 (Sreedharan et al. 2010). The wind is modeled based on its composite nature, which includes average, ramp, gust and turbulence components. Moreover, a solar photovoltaic generator is integrated at bus 6 through a transformer and bus 16; then, the bus 11 is modified by adding a synchronous generator through a transformer and bus 17 for representing the power generation from bio mass. The single-line diagram of the IEEE 14-bus system connected with the solar and wind power model is shown in Fig. 2.
Renewable resources integrated with Kerala grid
This system contains four synchronous generators connected at the buses 3 (Brahmapuram), 6 (Idukki), 17 (Nallalam) and 24 (Sabarigiri). The AVR and turbine governors are connected with the generators; then, the DFIG is placed at the buses 1 (Agali) and 23 (Ramakkalmedu). Similarly, two solar photovoltaic generators are integrated at the buses 4 (CASF) and 11 (KSEBSF). The single-line diagram of the Kerala grid with wind and solar power modeled is depicted in Fig. 3.